Setra FLEX™ Not Alarming
There are several things to check on the Setra FLEX™ to ensure you are set up to ALARM.
First, be sure the room is not in STANDBY mode. You can go to the PROFILE list and check the status there.
Under the ROOM tab make sure that the parameter you want to alarm is ENABLED.
Next go to the ALARM setup and make sure the lo and/or hi alarms are ENABLED.
In the ROOM PROFILE screen, make sure the ALARM ENABLE is ENABLED.
In the ALARM SETTINGS screen make sure the AUDIBLE ALARM is ENABLED.